Notes Switch travel diagram
  Contact closed
  Contact open
  Setting range
  Break point
  Positive opening sequence/- angle
VS  adjustable range of NO contact
  adjustable range of NC contact
N   after travel
Deutsch  English  Francais  Nederlands  Italiano  Español  Português  Suomi  Svenska  Norsk  Dansk  Polska  日本語  Türkiye  中文  Português-br  
  
• AS-Interface M12 connector
• Metal enclosure
• Wide range of alternative actuators
• Good resistance to oil and petroleum spirit
• 40,5 mm x 96 mm x 38 mm
• Actuator heads can be repositioned by 4 x 90°
• Mounting details to EN 50047
• AS-Interface LED and status display
• Integrated AS-Interface
• Suitable for AS-i Power24
• Actuation from bottom parallel to the switch, therefore only suitable for small housings.

 
 
Ordering details
 
Product type descriptionT3K 335 ST-AS - Ordering suffix
Article numberT3K 335 ST-AS
EAN Code
eCl@ss27-27-26-01
 
Approval
 
Approval

 
Classification
 
StandardsEN ISO 13849-1, IEC 61508
PLup c
Control categoryup 1
PFH1.14 x 10−6 /
- noticeup to max. 100000 switching cycles/year
SILup 1
Mission time20 Years
If a fault exclusion for hazardous damage of the 1-channel mechanics is authorized and an adequate protection against tampering is ensured, suitable for use up to:
StandardsEN ISO 13849-1, IEC 61508
PLup d
Control categoryup 3
PFH value1.01 x 10−7 /
- noticeup to max. 100000 switching cycles/year
SILup 2
Mission time20 Years
 
Global Properties
 
Permanent lightAS - 335 Winkelhebel 3K
StandardsEN 50295, EN 60947-5-1, EN ISO 13849-1, IEC 61508
Compliance with the Directives (Y/N) Yes
Suitable for safety functions (Y/N)Yes
Materials
- Material of the housingsZink
- Material of the connectorMetal film
- Material of the contactsSilver
Housing coatingpainted
Housing construction formNorm construction design
Weight
 
Mechanical data
 
Design of actuating elementAngle roller lever
Design of electrical connectionconnector plug M12, 5-pole, can be rotated
Mechanical life1.000.000 operations
Switching frequency5000
restistance to shock30 / 11
Resistance to vibration10 … 150, Amplitude 0,35 / 5
Actuating speed with actuating angle 30° to switch axis
- Min. Actuating speed
- Max. Actuating speed0,5
 
Ambient conditions
 
Ambient temperature
- Min. environmental temperature−25
- Max. environmental temperature+60
- Min. Storage and transport temperature−25
- Max. Storage and transport temperature+85
Relative humidity30 … 95
- non-condensing
- non-icing
Protection classIP67 to IEC/EN 60529
 
Electrical data
 
Design of control elementOpener (NC)
Switching principleCreep circuit element
- positive break NC contact
Number of auxiliary contacts0
Number of safety contacts2
Rated impulse withstand voltage800
Rated insulation voltage32
Thermal test current10 A
Utilisation categoryAC-15: 230 V / 4 A,
DC-13: 24 V / 1 A
Max. fuse rating6 A gG D-fuse
 
Electrical data - AS interface
 
AS-i Supply voltage18 … 31.6 VDC, Protection against polarity reversal
AS-i operating current≤ 50
AS-i Device insulationinternally short-circuit proof
AS-i Specification
- versionV 3.0
- ProfileS-0.B.F.F
AS-i Inputs
- Channel 1Data bits DI 0/DI 1= dynamic code transmission
- Channel 2Data bits DI 2/DI 3= dynamic code transmission
AS-i OutputsDO 0 … DO 3 not used
AS-i Parameter bitsP1 … P3 not used
- P0Channel 2 switched
AS-i input module address0
- Default on address 0, programmable via the AS-Interface Master or Hand-held programming device
 
LED switching conditions display
 
LED switching conditions display (Y/N)Yes
AS-i LED switching conditions display
(1) yellow LEDChannel 1 / AS-i SaW Bit 0,1
(2) green/red LED (AS-i duo LED)Supply voltage / Communication error / slave address = 0
(3) yellow LEDChannel 2 / AS-i SaW Bit 2,3
 
ATEX
 
Explosion protection categories for gasesNone
Explosion protected category for dustsNone
 
Dimensions
 
Dimensions of the sensor
- Width of sensor58.25
- Height of sensor152.5
- Length of sensor38
 
Pin assignment
 
1AS interface +
2None
3AS interface −
4None
5Functional earth connection
 
notice
 
The addressing must take place via the M12 connector or the flat cable connection.
 
Switch travel diagram
 


Notes Switch travel diagram
  Contact closed
  Contact open
  Setting range
  Break point
  Positive opening sequence/- angle
VS  adjustable range of NO contact
  adjustable range of NC contact
N   after travel
 
Ordering suffix
 
The applicable ordering suffix is added at the end of the part number of the safety switch.
Order example: T3K 335 ST-AS-FK
...-FK $missingName$


K.A. Schmersal GmbH & Co. KG, Möddinghofe 30, D-42279 Wuppertal
The data and values have been checked throroughly. Technical modifications and errors excepted.
Generiert am 23.02.2019 - 07:44:56h Kasbase 3.3.0.F.64I