Notes Switch travel diagram
  Contact closed
  Contact open
  Setting range
  Break point
  Positive opening sequence/- angle
VS  adjustable range of NO contact
  adjustable range of NC contact
N   after travel
Deutsch  English  Francais  Nederlands  Italiano  Español  Português  Suomi  Svenska  Norsk  Dansk  Polska  日本語  Türkiye  中文  Português-br  
  
• Metal enclosure
• Wide range of alternative actuators
• Good resistance to oil and petroleum spirit
• 66,7 mm x 76 mm x 38 mm
• Actuator heads can be repositioned by 4 x 90°
• Including Ex-certified screwed cable gland and screw plug
• Mounting details to EN 50041
• 3 cable entries M 20 x 1.5
• Ex certified

 
 
Ordering details
 
Product type descriptionEX-TS 355-11Z-3G/D - Ordering suffix
Article number10EX-TS 355-11Z/3G/D
EAN Code
eCl@ss27-27-26-01
 
Approval
 
Approval
 
Classification
 
StandardsISO 13849-1
B10d Normally-closed contact (NC)20.000.000
Mission time20 Years
notice
 
Global Properties
 
Permanent lightEX-T 355 Druckbolzen S
StandardsIEC 60947-5-1, EN 60079-0, EN 60079-15, EN 60079-31, BG-GS-ET-15
Compliance with the Directives (Y/N) Yes
Suitable for safety functions (Y/N)Yes
Actuator typeB to EN 50041
Materials
- Material of the housingslight alloy die-casting
- Material of the contactsSilver
Housing coatingpainted
Housing construction formNorm construction design
Weight
 
Mechanical data
 
Design of electrical connectionScrew connection
Cable cross-section of the cable glands
- Min. Cable cross-section of the cable glands7
- Max. Cable cross-section of the cable glands12
Cable section
- Min. Cable section0,75
- Max. Cable section2.5
AWG-Number13
Mechanical life30.000.000 operations
Switching frequency5000
noticeAll indications about the cable section are including the conductor ferrules.
Design of actuating elementPlunger
Actuating force17
Bounce duration< 2
Switchover timein accordance with actuating speed
Impact energy1
Actuating speed for vertical actuation
- Min. Actuating speed
- Max. Actuating speed0,5
 
Ambient conditions
 
Ambient temperature
- Min. environmental temperature−20
- Max. environmental temperature+60
Protection classIP67
 
Electrical data
 
Design of control elementNormally open contact (NO), Opener (NC)
Switching principleSlow action
- positive break NC contact
Number of auxiliary contacts1
Number of safety contacts1
Rated impulse withstand voltage6
Rated insulation voltage500
Thermal test current10 A
Utilisation categoryAC-15: 230 V / 4 A,
DC-13: 24 V / 1 A
Max. fuse rating6 A gG D-fuse
 
ATEX
 
EX-markingEX II 3G Ex nC IIC T5 Gc X, EX II 3D Ex tc IIIC T90°C Dc X
Explosion protection categories for gasesATEX gas ex-protection, Cat. 3
Explosion protection Zones for gases2
Explosion protected category for dustsATEX dust ex-protection, Cat. 3
Explosion protection Zones for dusts22
 
Dimensions
 
Dimensions of the sensor
- Width of sensor40.5
- Height of sensor103.5
- Length of sensor38
 
Keywords
 
KeywordsEx, EEx, ATEX, Ex 235, Ex 235, 235 Ex, 235ex, 235ex, ATEX 235
 
Switch travel diagram
 


Notes Switch travel diagram
  Contact closed
  Contact open
  Setting range
  Break point
  Positive opening sequence/- angle
VS  adjustable range of NO contact
  adjustable range of NC contact
N   after travel
 
Ordering suffix
 
The applicable ordering suffix is added at the end of the part number of the safety switch.
Order example: EX-TS 355-11Z-3G/D-1297
...-1297 Enclosure with transverse slotted holes

...-1637 0,3 µm gold-plated contacts


K.A. Schmersal GmbH & Co. KG, Möddinghofe 30, D-42279 Wuppertal
The data and values have been checked throroughly. Technical modifications and errors excepted.
Generiert am 22.04.2019 - 17:14:26h Kasbase 3.3.0.F.64I