|  Preferred typ |
|
Ordering details |
|
Product type description | PROTECT-PE-11 |
Article number | 101210943 |
EAN Code | 4030661395500 |
eCl@ss | 27-37-19-01 |
|
Approval |
|
Approval | USA/CAN
EAC |
|
Classification |
|
Standards | EN ISO 13849-1, IEC 61508, EN 60947-5-1 |
PL | up d (STOP 0) |
Control category | up 3 (STOP 0) |
DC | > 60% (STOP 0) |
CCF | > 65 points |
PFH value | ≤ 2 x 10-7/h (STOP 1) |
- notice | up to max. 36.500 switching cycles/year and at max. 60% contact load |
SIL | up 2 (STOP 0) |
Mission time | 20 Years |
- notice | The PFH value is applicable for the combinations listed in the table for contact load (K) (current through enabling paths) and switching cycle number (n-op/y). In case of 365 operating days per year and a 24-hour operation, this results in the specified switching cycle times (t-cycle) for the relay contacts. Diverging applications on request.
 |
|
Global Properties |
|
Permanent light | PROTECT-PE |
Standards | IEC/EN 60204-1, EN 60947-5-1, EN ISO 13849-1, IEC 61508 |
Compliance with the Directives (Y/N)  | Yes |
Climatic stress | EN 60068-2-78 |
Mounting | snaps onto standard DIN rail to EN 60715 |
Terminal designations | IEC/EN 60947-1 |
Materials |
- Material of the housings | Plastic, glass-fibre reinforced thermoplastic, ventilated |
Weight | 220 |
Start conditions | Automatic |
Start input (Y/N) | No |
Feedback circuit (Y/N) | No |
Start-up test (Y/N) | No |
Automatic reset function (Y/N) | Yes |
Reset with edge detection (Y/N) | No |
Pull-in delay |
- ON delay with automatic start | typ. 10 ms |
Drop-out delay |
- Drop-out delay in case of power failure | ≤ 60 |
- Drop-out delay in case of emergency stop | ≤ 10 |
|
Mechanical data |
|
Connection type | Cage clamps |
Cable section |
- Min. Cable section | 0,08 |
- Max. Cable section | 2.5 |
Pre-wired cable | rigid or flexible |
Tightening torque for the terminals | 0,6 |
Detachable terminals (Y/N) | No |
Mechanical life | 10.000.000 operations |
Electrical lifetime | Derating curve available on request |
restistance to shock | 30 g / 11 ms |
Resistance to vibration To EN 60068-2-6 | 10…55 HZ, Amplitude 0,35 mm, ± 15 % |
|
Ambient conditions |
|
Ambient temperature |
- Min. environmental temperature | −25 |
- Max. environmental temperature | +55 |
Storage and transport temperature |
- Min. Storage and transport temperature | −40 |
- Max. Storage and transport temperature | +85 |
Protection class |
- Protection class-Enclosure | IP20 |
- Protection class-Terminals | IP20 |
- Protection class-Clearance | IP20 |
Air clearances and creepage distances To IEC/EN 60664-1 |
- Rated impulse withstand voltage Uimp | 4 kV |
- Overvoltage category | III To VDE 0110 |
- Degree of pollution | 2 To VDE 0110 |
|
Electromagnetic compatibility (EMC) |
|
EMC rating | conforming to EMC Directive |
|
Electrical data |
|
Rated DC voltage for controls |
- Max. rated DC voltage for controls | 21.1 |
- Max. rated DC voltage for controls | 28.8 |
Rated AC voltage for controls, 50 Hz |
- Min. rated AC voltage for controls, 50 Hz | 21.1 |
- Max. rated AC voltage for controls, 50 Hz | 26.4 |
Rated AC voltage for controls, 60 Hz |
- Min. rated AC voltage for controls, 60 Hz | 21.1 |
- Max. rated AC voltage for controls, 60 Hz | 26.4 |
Contact resistance | max. 100 mΩ |
Power consumption | max. 1.7 W; plus signalling outputs Y1…Y5 |
Type of actuation | DC |
Rated operating voltage Ue | 24 VDC −12% / +20%, residual ripple max. 10% |
Operating current Ie | 0,075 A; plus signalling outputs Y1…Y5 |
Electronic protection (Y/N) | Yes |
Fuse rating for the operating voltage | Internal electronic trip, tripping current > 0,3 A |
Current and tension on control circuits | 24 VDC, 10 mA |
|
Inputs |
|
Number of shutters | 1 |
Number of openers | 1 |
Input resistance | approx. 2900 Ω at GND or at Ue |
Input signal "1" | 19 - 28.8 VDC |
Input signal "0" | 0 - 1 VDC |
Conduction resistance | max. 40 Ω |
|
Outputs |
|
Stop category | 0 |
Number of safety contacts | 0 |
Number of auxiliary contacts | 2 (13-14; 23- 24) |
Number of signalling outputs | 7 ( Y1-Y5) |
Switching capacity |
- Switching capacity of the safety contacts | max. 24 VDC, 2 A ohmic (inductive in case of appropriate protective wiring) |
- Switching capacity of the signaling/diagnostic outputs | 24 VDC / 100 mA |
Fuse rating |
- Protection of the safety contacts | 2 A slow blow |
- Fuse rating for the signaling/diagnostic outputs | Internal electronic trip, tripping current > 0,75 A |
Utilisation category To EN 60947-5-1 | DC-13: 24 V / 2 A |
Number of undelayed semi-conductor outputs with signaling function | 0 |
Number of undelayed outputs with signaling function (with contact) | 9 |
Number of delayed semi-conductor outputs with signaling function. | 0 |
Number of delayed outputs with signalling function (with contact). | 0 |
Number of secure undelayed semi-conductor outputs with signaling function | 0 |
Number of secure, undelayed outputs with signaling function, with contact. | 0 |
Number of secure, delayed semi-conductor outputs with signaling function | 0 |
Number of secure, delayed outputs with signaling function (with contact). | 0 |
Outputs with antivalent safety contacts (Y/N) | No |
|
LED switching conditions display |
|
LED switching conditions display (Y/N) | Yes |
Number of LED´s | 6 |
LED switching conditions display |
- The integrated LEDs indicate the following operating states. |
- Position relay K1 |
- Position relay K2 |
- Position relay K3 |
- Position relay K4 |
- Internal operating voltage Ui |
- LED’s or signalling outputs signalise an opened protective device or emergency stops. |
- Monitoring effected on both contact circuits of the sensor. |
- When the safety guard or the emergency stop circuit is opened, a 24V signal is switched at each output concerned (Y1...Y5) and the assigned LED is lit. |
|
Miscellaneous data |
|
Applications | Emergency-Stop button
Pull-wire emergency stop switches
Guard system
Safety sensor
Safety light curtain |
|
Dimensions |
|
Dimensions |
- Width | 65.5 mm |
- Height | 126 mm |
- Depth | 61 mm |
|
notice |
|
Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit. |
|
notice - Wiring example |
|
Start level: Depends on the wiring of the safety relay module. |
Sensor level: 2-channel control of magnetic safety switches according to EN 60947-5-3 |
Output level: 2-channel control of a downstream safety relay module |
The control recognises cross-short, cable break and earth leakages in the monitoring circuit. |
If the inputs S1, S3, S5 and S7 are not used, they have to be bridged to + |
If the inputs S2, S4, S6 and S8 are not used, they have to be bridged to - |
The safety relay modules must be suitable for signal processing for single or dual-channel floating NC-contacts |
Start and actuator configuration has to be effected in accordance with the data sheet |
The wiring diagram is shown with guard doors closed and in de-energised condition. |
|
Keywords |
|
Keywords | PROTECT |
|
K.A. Schmersal GmbH & Co. KG, Möddinghofe 30, D-42279 Wuppertal The data and values have been checked throroughly. Technical modifications and errors excepted. Generiert am
19.02.2019 -
09:44:51h Kasbase 3.3.0.F.64I |