Notes Switch travel diagram
  Contact closed
  Contact open
  Setting range
  Break point
  Positive opening sequence/- angle
VS  adjustable range of NO contact
  adjustable range of NC contact
N   after travel
Deutsch  English  Francais  Nederlands  Italiano  Español  Português  Suomi  Svenska  Norsk  Dansk  Polska  日本語  Türkiye  中文  Português-br  
  
Home ->
Safety sensors  ->  CSS 30  ->  CSS 15-30-2P+D-M-L
• Metal enclosure
• Max. 16 sensors can be wired in series.
• Pre-wired cable, 7-pole
• Ø M30
• High repeat accuracy of the switching points
• Max. length of the sensor chain 200 m
• 2 short-circuit proof PNP safety outputs
• Integral cross-short, wire-breakage and external voltage monitoring of the safety cables up to the control cabinet

 
 
Ordering details
 
Product type descriptionCSS 15-30-2P+D-M-L
Article number101209841
EAN Code4030661386805
eCl@ss27-27-24-01
 
Approval
 
Approval BG
EAC
 
Classification
 
StandardsEN ISO 13849-1, IEC 61508, IEC 60947-5-3
PLup e
Control categorybis 4
PFH2.5 x 10 -9/h
SILbis 3
Mission time20 Years
ClassificationPDF-M
 
Global Properties
 
Permanent lightCSS 30
StandardsIEC 60947-5-3, IEC 61508
Compliance with the Directives (Y/N) Yes
Suitable for safety functions (Y/N)Yes
FunctionSensor for series wiring
Series-wiringup to 16 components
Length of the sensor chainmax. 200 m
Active principleinductive
Materials
- Material of the active surfacePlastic
- Material of the housingsBrass, nickel-plated
Housing construction formcylinder, thread
Weight248
Diagnostic output (Y/N)Yes
Reaction time< 30
Duration of risk≤ 30
Cascadable (Y/N)Yes
Recommended actuatorCST 30-1, CST 34-S-3
 
Mechanical data
 
Design of electrical connectionCable
Cable length2
Conductors0,25
AWG-Number23
mechanical installation conditionsnot flush
Actuating planesActuation from top
Active areafront
Switch distance Sn12 mm / 15 mm
Actuator CST 30-115
Actuator CST 34-S-312
Ensured switch distance ON Sao10 mm / 12 mm
Actuator CST 30-112
Actuator CST 34-S-310
Ensured switch distance OFF Sar16 mm / 19 mm
Actuator CST 30-119
Actuator CST 34-S-316
hysteresis< 2 mm
Repeat accuracy R R< 1 mm
restistance to shock30 g / 11 ms
Resistance to vibration10 … 55 HZ, Amplitude 1 mm
 
Ambient conditions
 
Ambient temperature
- Min. environmental temperature−25
- Max. environmental temperature+55
Storage and transport temperature
- Min. Storage and transport temperature−25
- Max. Storage and transport temperature+85
Protection classIP65, IP67 to IEC/EN 60529
IP69K to DIN 40050-9
Protection ratingII
Air clearances and creepage distances To IEC/EN 60664-1
- Rated impulse withstand voltage Uimp0,8 kV
- Overvoltage categoryIII
- Degree of pollution3
 
Electromagnetic compatibility (EMC)
 
EMC ratingto IEC 61000-6-2
Interfering radiationto IEC 61000-6-4
 
Electrical data
 
Cross circuit/short circuit recognition possible (Y/N)Yes
Voltage typeDC
Switch frequency3
Rated insulation voltage Ui32 VAC/DC
Rated operating voltage Ue (stabilised PELV)
- Min. Rated operating voltage20.4 VDC
- Max. Rated operating voltage26.4 VDC
Operating current Ie1.1 A
No-load current I00,05 A
Required rated short-circuit current100 A
noticeThe cable section of the interconnecting cable must be observed for both wiring variants! Cable length and cable section alter the voltage drop depending on the output current
 
Electrical data - Safety inputs
 
Safety inputsX1 and X2
 
Electrical data - Safety outputs
 
Safety outputsY1 and Y2
Fuse ratingshort-circuit proof
Design of control outputp-type
Number of secure semi-conductor outputs2
Max. output current at secured output0,25 A
Rated operating voltagemin. (Ue − 0,5 V)
Residual current Ir≤ 0,5 mA
Operating current Iemax. 0,5 A
- Ambient temperature: −25 °C … +65 °C≤ 0,2 A
Minimum operating current Im0,5 mA
- Ambient temperature: −25 °C … +70 °C≤ 0,1 A
Utilisation categoryDC-12: 24 V / 0,5 A
DC-13: 24 V / 0,5 A
Voltage drop Ud0,5 V
 
Electrical data - Diagnostic output
 
Serial diagnostics (Y/N)No
Fuse ratingshort-circuit proof
Design of control outputp-type
Number of semi-conductor outputs with signaling function1
Rated operating voltagemin. (Ue − 4 V)
Operating current Iemax. 0,05 A
Voltage drop Ud< 4 V
Utilisation categoryDC-12: 24 V / 0,05 A
DC-13: 24 V / 0,05 A
 
LED switching conditions display
 
LED switching conditions display (Y/N)Yes
Number of LED´s1
 
ATEX
 
Explosion protection categories for gasesNone
Explosion protected category for dustsNone
 
Dimensions
 
Dimensions of the sensor
- Length of sensor101
- Diameter of sensorM30
 
Pin assignment
 
1 - A1 UeBrown
2 - X1 Safety input 1violet
3 - A2 GNDBlue
4 - Y1 Safety output 1Black
5 - OUT Diagnostic outputGrey
6 - X2 Safety input 2White
7 - Y2 Safety output 2red
 
notice
 
Requirements for the safety monitoring moduleThe safety monitoring module must tolerate internal functional tests of the safety outputs for 250 μs –1500 μs.
The 250 μs switch-off time of the safety sensor additionally will be extended depending on the cable length and the capacity of the cable used. Typically, a switch-off time of 500 μs is reached with a 100 m connecting cable.
 
Included in delivery
 
Actuators must be ordered separately.
Mounting accessories Nuts M302 piece
 
Diagram
 


Note Diagram
  positive break NC contact
  active
  no active
  Normally-open contact
  Normally-closed contact

K.A. Schmersal GmbH & Co. KG, Möddinghofe 30, D-42279 Wuppertal
The data and values have been checked throroughly. Technical modifications and errors excepted.
Generiert am 20.04.2019 - 15:00:49h Kasbase 3.3.0.F.64I