Notes Switch travel diagram
  Contact closed
  Contact open
  Setting range
  Break point
  Positive opening sequence/- angle
VS  adjustable range of NO contact
  adjustable range of NC contact
N   after travel
Deutsch  English  Francais  Nederlands  Italiano  Español  Português  Suomi  Svenska  Norsk  Dansk  Polska  日本語  Türkiye  中文  Português-br  
  
• PROFIBUS Gateway SD-I-DP-V0-2 to convert serial diagnostic signals to the PROFIBUS DP protocol
• The PROFIBUS Gateway SD-I-DP-V0-2 is a PROFIBUS slave
• Protection class IP 10 device for control cabinet mounting, for standard DIN rails

 
Preferred typ
 
Ordering details
 
Product type descriptionSD-I-DP-V0-2
Article number101192805
EAN Code4030661353951
eCl@ss27-27-24-90
 
Approval
 
ApprovalNone
 
Global Properties
 
Permanent lightSD-Gateway
Standards-
Compliance with the Directives (Y/N) Yes
Mountingsnaps onto standard DIN rail to EN 60715
Weight120
DIP switch, 8-poleS1 … S7: addressing as Profibus slave;
S8: automatic addressing of the serial devices
 
Mechanical data
 
Design of electrical connectionCage clamps
restistance to shock15 g / 11 ms
Resistance to vibration To EN 60068-2-65 … 9 HZ, Amplitude 3.5 mm;
9 … 150 HZ, with 1 g
 
Ambient conditions
 
Ambient temperature
- Min. environmental temperature−5
- Max. environmental temperature+55
Storage and transport temperature
- Min. Storage and transport temperature−25
- Max. Storage and transport temperature+85
Protection class
- Protection class-EnclosureIP10
Air clearances and creepage distances To IEC/EN 60664-1
- Rated impulse withstand voltage Uimp0,5 kV
- Overvoltage categoryII To VDE 0110
- Degree of pollution2 To VDE 0110
 
Interface
 
Interface9-pole SUB-D connector, default Profibus connection (DP-A, DP-B, 5V, GND)
ProtocolProfibus-DP -V0 upwards compatible
Transfer rate9600 Baud ... 12 MBaud
GSD fileKAS_0b13.GSD DOWNLOAD
 
Electrical data
 
Clip SDconnection for max. 31 devices in the serial diagnostics
Clip 24 V+ 24 VDC power supply
Clip 0 VGND of the power supply and GND of the diagnostic line
Rated insulation voltage Ui32 V
Rated operating voltage Ue24 VDC, - 15 % / + 20 % (stabilised PELV)
Operating current Iemax. 250 mA
Max. fuse ratinginternal fuse to EN 60127, PolySwitch 0.5 A / 60 V
 
LED switching conditions display
 
LED switching conditions display (Y/N)Yes
Number of LED´s4
LED switching conditions display
- The integrated LEDs indicate the following operating states.
- PB Continuous signal redError PROFIBUS
- PB Flashing signalInitialisation PROFIBUS
- SD Continuous signal redError SD Gateway
- SD Flashing signalInitialisation SD Gateway
- T Continuous signal yellowSD initialisation error, teaching required
- T Flashing signalInitialization error SD device addresses, teaching required
- ON Continuous signal greenPower supply on
 
Miscellaneous data
 
Applications Guard system
Safety sensor
 
Dimensions
 
Dimensions
- Width50 mm
- Height72 mm
- Depth97 mm
 
notice
 
Detailed functions, see programming and configuration manual of the SD Gateway
 
notice - Wiring example
 
Serial diagnostics of series-wired safety sensors/solenoid interlocks
Devices with serial diagnostic option: AZ 200, AZM 200, CSS 30S, CSS 34, MZM 100
 
Keywords
 
Search keysPROFIBUS, SD Gateway

K.A. Schmersal GmbH & Co. KG, Möddinghofe 30, D-42279 Wuppertal
The data and values have been checked throroughly. Technical modifications and errors excepted.
Generiert am 18.07.2019 - 14:14:29h Kasbase 3.3.0.F.64I