• Monitoring of BNS range magnetic safety sensors
• 1 safety contact, STOP 0
• 2 Signalling outputs

 
 
Ordering details
 
Product type descriptionAES 2136
Article number101181677
EAN Code4030661323084
eCl@ss27-37-19-01
 
Approval
 
Approval BG
USA/CAN
EAC
 
Classification
 
StandardsEN ISO 13849-1, IEC 61508
PLup d
Control categoryup 3
PFH value1.0 x 10-7/h
SILup 2
Mission time20 Years
PFHd
Switching frequency c
MTTFd
ClassificationPDF-M
 
Global Properties
 
Permanent lightAES 213x
StandardsIEC/EN 60204-1, EN 60947-5-1, IEC 60947-5-3, IEC 61508, BG-GS-ET-14, BG-GS-ET-20
Compliance with the Directives (Y/N) Yes
Climatic stressIEC 60947-5-3, BG-GS-ET-14
Mountingsnaps onto standard DIN rail to EN 60715
Terminal designationsIEC/EN 60947-1
Materials
- Material of the housingsPlastic, glass-fibre reinforced thermoplastic
- Material of the contactsAg-Ni, Au
Weight280
Start input (Y/N)No
Feedback circuit (Y/N)No
Start-up test (Y/N)Yes
Reset after disconnection of supply voltage (Y/N)Yes
Automatic reset function (Y/N)Yes
Reset with edge detection (Y/N)No
Pull-in delay
- ON delay with automatic startadjustable 0,1 / 1.0 s
Drop-out delay
- Drop-out delay in case of emergency stop< 50
 
Mechanical data
 
Connection typeScrew connection
Cable section
- Min. Cable section0,2
- Max. Cable section2.5
Pre-wired cablerigid or flexible
Tightening torque for the terminals0,6
Detachable terminals (Y/N)No
Mechanical life50.000.000 operations
Electrical lifetime100.000 operations for 230 VAC, 6 A (cos φ = 1)
restistance to shock30 g / 11 ms
Resistance to vibration To EN 60068-2-610…55 HZ, Amplitude 0,35 mm, ± 15 %
 
Ambient conditions
 
Ambient temperature
- Min. environmental temperature0
- Max. environmental temperature+55
Storage and transport temperature
- Min. Storage and transport temperature−25
- Max. Storage and transport temperature+70
Protection class
- Protection class-EnclosureIP40
- Protection class-TerminalsIP20
- Protection class-ClearanceIP54
Air clearances and creepage distances To IEC/EN 60664-1
- Rated impulse withstand voltage Uimp4.8 kV
- Overvoltage categoryIII To VDE 0110
- Degree of pollution2 To VDE 0110
 
Electromagnetic compatibility (EMC)
 
EMC rating10 V/m
 
Electrical data
 
Rated DC voltage for controls
- Max. rated DC voltage for controls20.4
- Max. rated DC voltage for controls253 VDC
Rated AC voltage for controls, 50 Hz
- Min. rated AC voltage for controls, 50 Hz20.4 VAC
- Max. rated AC voltage for controls, 50 Hz253 VAC
Rated AC voltage for controls, 60 Hz
- Min. rated AC voltage for controls, 60 Hz20.4 VAC
- Max. rated AC voltage for controls, 60 Hz253 VAC
Contact resistancemax. 100 mΩ
Power consumption5
Type of actuationDC
Switch frequency3
Rated insulation voltage Ui250 V
Rated operating voltage Ue24 … 230 VAC/DC
Thermal test current Ithe4 A
Operating current Ie0,2 A
Electronic protection (Y/N)No
 
Inputs
 
Monitored inputs
- Short-circuit recognition (Y/N)Yes
- Wire breakage detection (Y/N)Yes
- Earth connection detection (Y/N)No
Number of shuttersadjustable 1 - >0
Number of openersadjustable 1 - >2
Input resistanceapprox. 4000 Ω at GND
Input signal "1"10 … 30 VDC
Input signal "0"0 … 2 VDC
Cable length1000 m with 1.5 mm² (for Rated voltage)
 
Outputs
 
Stop category0
Number of safety contacts1
Number of auxiliary contacts0
Number of signalling outputs2
Switching capacity
- Switching capacity of the safety contactsmin. 10 mA, max. 4 A
- Switching capacity of the signaling/diagnostic outputsY1, Y2: max. 100 mA
Fuse rating
- Protection of the safety contacts4 A gG D-fuse
- Fuse rating for the signaling/diagnostic outputsshort-circuit proof
Signalling outputY1: (X5 / X6 without bridge) Authorized operation (X5 / X6 with bridge) guard open
Y2: (X5 / X6 without bridge) None Authorized operation (X5 / X6 with bridge) Error
Utilisation category To EN 60947-5-1AC-15: 230 V / 3 A
DC-13: 24 V / 2 A
Number of undelayed semi-conductor outputs with signaling function2
Number of undelayed outputs with signaling function (with contact)0
Number of delayed semi-conductor outputs with signaling function.0
Number of delayed outputs with signalling function (with contact).0
Number of secure undelayed semi-conductor outputs with signaling function0
Number of secure, undelayed outputs with signaling function, with contact.0
Number of secure, delayed semi-conductor outputs with signaling function0
Number of secure, delayed outputs with signaling function (with contact).0
 
LED switching conditions display
 
LED switching conditions display (Y/N)Yes
Number of LED´s1
 
Integral system diagnosis $missingShortName$
 
Integral system diagnosis ISD
- The following faults are registered by the safety monitoring modules and indicated by ISD
- Failure of door contacts to open or close
- Cross-wire or short-circuit monitoring of the switch connections
- Interruption of the switch connections
- Failure of the safety relay to pull-in or drop-out
- Fault on the input circuits or the relay control circuits of the safety monitoring module
 
Miscellaneous data
 
Applications Safety sensor
Guard system
 
Dimensions
 
Dimensions
- Width45 mm
- Height100 mm
- Depth121 mm
 
notice
 
Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.
 
notice - Wiring example
 
To secure a guard door up to PL 3 and Category #03#
Monitoring 1 guard door(s), each with a magnetic safety sensor of the BNS range
Modification for 2 NC contacts:
The safety monitoring module can be modified to monitor two NC contacts by bridging the terminals X3 and X4. The short-circuit recognition between connections then becomes inoperative.
Inversion of the output function:
By establishing a bridge between X5 and X6, the output function of the additional outputs can be altered. This control can also be realised when e.g. a PLC is running (24 VDC at terminal X6).
Expansion of the enable delay time
The enable delay time can be increased from 0,1 s to 1 s by mounting a jumper connection between the terminals X7 and X8.
The wiring diagram is shown with guard doors closed and in de-energised condition.
The ISD tables (Intergral System Diagnostics) for analysis of the fault indications and their causes are shown in the appendix.