Ordering details
 
Product type descriptionBNS 16 ST3-AS V
Article number101178188
EAN Code4030661310077
eCl@ss27-27-24-02
 
Approval
 
Approval AS-i
USA/CAN
TÜV
 
Classification
 
StandardsEN ISO 13849-1, IEC 61508
PLup e
Control categorybis 4
PFH7.42 x 10-9 / h
- noticeup to max. 500.000 switching cycles/year
SILup 3
Mission time20 Years
 
Global Properties
 
Permanent lightBNS 16 AS
StandardsEN 50295, IEC 60947-5-3, EN ISO 13849-1, IEC 61508
Compliance with the Directives (Y/N) Yes
Materials
- Material of the housingsPlastic, glass-fibre reinforced thermoplastic
Weight150
Coding available (Y/N)Yes
Response time< 100
Recommended actuatorBPS 16
 
Mechanical data
 
Design of electrical connectionconnector plug M12, 4-pole
connectorleft
mechanical installation conditionsquasi-flush
Active areafront side
Ensured switch distance ON Sao8 mm
Ensured switch distance OFF Sar18 mm
Repeat accuracy R RR ≤ 0,1 x Sao
Type of actuationMagnet
Direction of motionhead-on with regard to the active surface
restistance to shock30 g / 11 ms
Resistance to vibration10 … 55 HZ, Amplitude 1 mm
 
Ambient conditions
 
Ambient temperature
- Min. environmental temperature−25
- Max. environmental temperature+60
Storage and transport temperature
- Min. Storage and transport temperature−25
- Max. Storage and transport temperature+70
Protection classIP67 to IEC/EN 60529
Air clearances and creepage distances To IEC/EN 60664-1
- Rated impulse withstand voltage Uimp0,8 kV
- Rated insulation voltage Ui32 VDC
- Overvoltage categoryIII
- Degree of pollution3
 
Electrical data - AS interface
 
AS-i Supply voltage26.5 … 31.6 VDC, Protection against polarity reversal
AS-i operating current≤ 50
AS-i Device insulationinternally short-circuit proof
AS-i Specification
- versionV 2.1
- ProfileS-0.B.F.E
- IO-Code0x0
- ID-Code0xB
- ID-Code10xF
- ID-Code20xE
AS-i Inputs
- Channel 1Data bits DI 0/DI 1= dynamic code transmission
- Channel 2Data bits DI 2/DI 3= dynamic code transmission
AS-i OutputsDO 0 … DO 3 not used
AS-i Parameter bitsP0 … P3 not used
AS-i input module address0
- Default on address 0, programmable via the AS-Interface Master or Hand-held programming device
 
LED switching conditions display
 
LED switching conditions display (Y/N)Yes
AS-i LED switching conditions display
AS-i LED switching conditions display
(1) green LEDSupply voltage
(2) red LEDCommunication error / slave address = 0
(3) yellow LEDEnabling status
 
ATEX
 
Explosion protection categories for gasesNone
Explosion protected category for dustsNone
 
Dimensions
 
Dimensions of the sensor
- Width of sensor40
- Height of sensor90
- Length of sensor38.5
 
Pin assignment
 
1AS-i +
2None
3AS-i −
4None
 
Included in delivery
 