• Multi-evaluation of up to 6 safety guards
• Suitable for signal processing of potential-free outputs, e.g. emergency stop command devices, position switches and solenoid interlocks
• 2 safety contacts, STOP 0
• 6 Signalling outputs

 
Preferred typ
 
Ordering details
 
Product type descriptionSRB206ST-230V
Article number101174014
EAN Code4250116201860
Replaced article number 101177164
eCl@ss27-37-19-01
 
Approval
 
Approval USA/CAN
BG
 
Classification
 
StandardsEN ISO 13849-1, IEC 61508, EN 60947-5-1
PLup d (STOP 0)
Control categorybis 3 (STOP 0)
DC> 60% (STOP 0)
CCF> 65 points
PFH value≤ 2,0 x 10-7/h (STOP 0)
SILbis 3 (STOP 0)
Mission time20 Years
- noticeThe PFH value is applicable for the combinations listed in the table for contact load (K) (current through enabling paths) and switching cycle number (n-op/y).
In case of 365 operating days per year and a 24-hour operation, this results in the specified switching cycle times (t-cycle) for the relay contacts.
Diverging applications on request.
 
Global Properties
 
Permanent lightSRB206ST
StandardsIEC/EN 60204-1, EN 60947-5-1, EN ISO 13849-1, IEC 61508
Compliance with the Directives (Y/N) Yes
Climatic stressEN 60068-2-78
Mountingsnaps onto standard DIN rail to EN 60715
Terminal designationsIEC/EN 60947-1
Materials
- Material of the housingsPlastic, glass-fibre reinforced thermoplastic, ventilated
- Material of the contactsAgCdO, self-cleaning, positive action
Weight400
Start conditionsAutomatic or Start button (Optional monitored)
Start input (Y/N)Yes
Feedback circuit (Y/N)Yes
Start-up test (Y/N)No
Reset after disconnection of supply voltage (Y/N)No
Automatic reset function (Y/N)Yes
Reset with edge detection (Y/N)Yes
Pull-in delay
- ON delay with reset buttontyp. 50 ms
Drop-out delay
- Drop-out delay in case of emergency stop≤ 30 ms
 
Mechanical data
 
Connection typeScrew connection
Cable section
- Min. Cable section0,25
- Max. Cable section2.5
Pre-wired cablerigid or flexible
Tightening torque for the terminals0,6
Detachable terminals (Y/N)Yes
Mechanical life10.000.000 operations
Electrical lifetimeDerating curve available on request
restistance to shock30 g / 11 ms
Resistance to vibration To EN 60068-2-610…55 HZ, Amplitude 0,35 mm, ± 15 %
 
Ambient conditions
 
Ambient temperature
- Min. environmental temperature−25 °C
- Max. environmental temperature+45 °C
Storage and transport temperature
- Min. Storage and transport temperature−40 °C
- Max. Storage and transport temperature+85 °C
Protection class
- Protection class-EnclosureIP40
- Protection class-TerminalsIP20
- Protection class-ClearanceIP54
Air clearances and creepage distances To IEC/EN 60664-1
- Rated impulse withstand voltage Uimp4 kV
- Overvoltage categoryIII To VDE 0110
- Degree of pollution2 To VDE 0110
 
Electromagnetic compatibility (EMC)
 
EMC ratingconforming to EMC Directive
 
Electrical data
 
Rated DC voltage for controls
- Max. rated DC voltage for controls-
- Max. rated DC voltage for controls-
Rated AC voltage for controls, 50 Hz
- Min. rated AC voltage for controls, 50 Hz48
- Max. rated AC voltage for controls, 50 Hz240
Rated AC voltage for controls, 60 Hz
- Min. rated AC voltage for controls, 60 Hz48
- Max. rated AC voltage for controls, 60 Hz240
Contact resistancemax. 100 mΩ
Power consumption6.8 VA plus signalling outputs Y1-Y6
Type of actuationAC
Rated operating voltage Ue48 … 240 VAC
Operating current Ie0,275 A
Frequency range50 / 60
Electronic protection (Y/N)Yes
Fuse rating for the operating voltageprimary side: Safety fuse, tripping current > 1.0 A,
secondary side: Internal electronic trip, tripping current > 0,12 A
 
Inputs
 
Monitored inputs
- Short-circuit recognition (Y/N)No
- Wire breakage detection (Y/N)Yes
- Earth connection detection (Y/N)Yes
Number of shutters0 piece
Number of openers12 piece
Cable length1500 m with 1.5 mm²;
2500 m with 2.5 mm²
Conduction resistancemax. 40 Ω
 
Outputs
 
Stop category0
Number of safety contacts2 piece
Number of auxiliary contacts0 piece
Number of signalling outputs6 piece
Switching capacity
- Switching capacity of the safety contactsmax. 230 V, 6 A ohmic (inductive in case of appropriate protective wiring)
- Switching capacity of the auxiliary contacts24 VDC, 2 A
- Switching capacity of the signaling/diagnostic outputsY1…Y6: 24 VDC, 20 mA (externally through A1.1)
Fuse rating
- Protection of the safety contacts6.3 A slow blow
- Fuse rating for the signaling/diagnostic outputs200 mA slow blow
Utilisation category To EN 60947-5-1AC-15: 230 V / 6 A
DC-13: 24 V / 6 A
Number of undelayed semi-conductor outputs with signaling function0 piece
Number of undelayed outputs with signaling function (with contact)6 piece
Number of delayed semi-conductor outputs with signaling function.0 piece
Number of delayed outputs with signalling function (with contact).0 piece
Number of secure undelayed semi-conductor outputs with signaling function0 piece
Number of secure, undelayed outputs with signaling function, with contact.2 piece
Number of secure, delayed semi-conductor outputs with signaling function0 piece
Number of secure, delayed outputs with signaling function (with contact).0 piece
 
LED switching conditions display
 
LED switching conditions display (Y/N)Yes
Number of LED´s4
LED switching conditions display
- The integrated LEDs indicate the following operating states.
- Position relay K1
- Position relay K2
- Supply voltage
- Internal operating voltage Ui
 
Miscellaneous data
 
Applications Emergency-Stop button
Pull-wire emergency stop switches
Guard system
 
Dimensions
 
Dimensions
- Width45 mm
- Height100 mm
- Depth121 mm
 
notice
 
Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.
 
notice - Wiring example
 
Input level: The example shows a 2-channel control of a guard door monitoring with two position switches, whereof one with positive break, external reset button (R) and feedback circuit (H2).
If more guard doors are monitored, they must be connected according to the wiring table
The control system recognises wire-breakage and earth faults in the monitoring circuit.
Relay outputs: Suitable for 2 channel control, for increase in capacity or number of contacts by means of contactors or relays with positive-guided contacts.
A single failure in the sensors does not cause the safety to be lost
If the single failure occurs, the safety function will be maintained. Some, although not all, errors will be recognised. An accumulation of unrecognised errors could cause the safety function to be lost.
Automatic start: The automatic start is programmed by connecting the feedback circuit to the terminals X1/X3. If the feedback circuit is not required, establish a bridge
The wiring diagram is shown with guard doors closed and in de-energised condition.

K.A. Schmersal GmbH & Co. KG, Möddinghofe 30, D-42279 Wuppertal
The data and values have been checked throroughly. Technical modifications and errors excepted.