Ordering details |
|
Product type description | IFL 0,8-4-10P |
NOTICE: Not available! |
Article number | 101102256 |
EAN Code | 4030661048079 |
eCl@ss | 27-27-01-01 |
|
Global Properties |
|
Permanent light | IFL Ø 4 mm |
Standards | IEC/EN 60947-5-2; DIN VDE 0660-208 |
Compliance with the Directives (Y/N)  | Yes |
Operating resource protection class | None |
Materials |
- Material of the housings | Stainless steel |
- Material of the cable mantle | PVC |
- Material of the terminal fixing | Plastic |
Housing coating | None |
Housing construction form | cylinder smooth |
Weight | 35 |
|
Mechanical data |
|
Design of electrical connection | Cable |
Cable length | 2 |
Conductor with strain relief | No |
Conductors | 3 x 0,14 |
mechanical installation conditions | flush |
Switch distance Sn | 0,8 mm |
Reduction factor 1 met (Y/N) | No |
Protection circuit | inductive interference protection, Protection against polarity reversal, short-circuit and overload proof (pulsed) |
Pressure resistant (Y/N) | No |
|
Ambient conditions |
|
Ambient temperature |
- Min. environmental temperature | −25 |
- Max. environmental temperature | +70 |
Protection class | IP67 to IEC/EN 60529 |
|
Electrical data |
|
Design of control element | Normally open contact (NO) |
Number of wire | 3 |
Voltage type | DC, direct current |
Supply voltage UB |
- Min. supply voltage | 7 |
- Max. supply voltage | 35 |
Switch frequency | approx. 1000 HZ |
Voltage drop Ud | ≤ 2 V (100 mA) |
Operating current Ie | 100 mA |
No-load current I0 | < 2.5 mA |
|
Outputs |
|
Design of control output | PNP |
|
LED switching conditions display |
|
LED switching conditions display (Y/N) | Yes |
- yellow LED |
|
ATEX |
|
Explosion protection categories for gases | None |
Explosion protected category for dusts | None |
|
Dimensions |
|
Dimensions of the sensor |
- Width of sensor | 4 |
- Height of sensor | 4 |
- Length of sensor | 27.5 |
- Diameter of sensor | 4 mm |
|
notice |
|
Clamp H 4 is included in delivery |
|
Diagram |
|

Note Diagram
positive break NC contact
active
no active
Normally-open contact
Normally-closed contact |
|
K.A. Schmersal GmbH & Co. KG, Möddinghofe 30, D-42279 Wuppertal The data and values have been checked throroughly. Technical modifications and errors excepted. Generiert am
20.02.2019 -
17:15:49h Kasbase 3.3.0.F.64I |