 Preferred typ
|
|
|
| Ordering details
|
|
|
| Product type description
|
SRB 301ST-230V
|
| Article number
|
101177167
|
| EAN code
|
4030661307961
|
|
|
| Approval
|
|
|
| Approval
|
BG
USA/CAN
|
|
|
| Classification
|
|
|
| Standards
|
EN ISO 13849-1, IEC 61508, EN 60947-5-1
|
| PL
|
up e (STOP 0)
|
| Control category
|
up 4 (STOP 0)
|
| DC
|
99% (STOP 0)
|
| CCF
|
> 65 points
|
| PFH value
|
≤ 2,0 x 10-8/h (STOP 0)
|
| SIL
|
up 3 (STOP 0)
|
| Mission time
|
20 Years
|
| - notice
|
The PFH value is applicable for the combinations listed in the table for contact load (K) (current through enabling paths) and switching cycle number (n-op/y). In case of 365 operating days per year and a 24-hour operation, this results in the specified switching cycle times (t-cycle) for the relay contacts. Diverging applications on request.
|
|
|
| Global Properties
|
|
|
| Product name
|
SRB 301ST-230V
|
| Standards
|
IEC/EN 60204-1, EN 60947-5-1, EN ISO 13849-1, IEC 61508
|
Compliance with the Directives (Y/N)
|
Yes
|
| Climatic stress
|
EN 60068-2-78
|
| Mounting
|
snaps onto standard DIN rail to EN 60715
|
| Terminal designations
|
IEC/EN 60947-1
|
| Materials
|
| - Material of the housings
|
Plastic, glass-fibre reinforced thermoplastic, ventilated
|
| - Material of the contacts
|
, self-cleaning, positive action
|
| Weight
|
250 g
|
| Start conditions
|
Automatic or Start button
|
| Start input (Y/N)
|
Yes
|
| Feedback circuit (Y/N)
|
Yes
|
| Start-up test (Y/N)
|
No
|
| Reset after disconnection of supply voltage (Y/N)
|
| Automatic reset function (Y/N)
|
Yes
|
| Reset with edge detection (Y/N)
|
Yes
|
| Pull-in delay
|
| - ON delay with automatic start
|
30 ms
|
| Drop-out delay
|
| - Drop-out delay in case of power failure
|
100 ms (48 VAC); 300 ms (240 VAC)
|
| - Drop-out delay in case of emergency stop
|
≤ 30 ms
|
|
|
| Mechanical data
|
|
|
| Connection type
|
Screw connection
|
| Cable section
|
| - Min. Cable section
|
0,25 mm²
|
| - Max. Cable section
|
2.5 mm²
|
| Pre-wired cable
|
rigid or flexible
|
| Tightening torque for the terminals
|
0,6 Nm
|
| Detachable terminals (Y/N)
|
Yes
|
| Mechanical life
|
10.000.000 operations
|
| Electrical lifetime
|
Derating curve available on request
|
| restistance to shock
|
30 g / 11 ms
|
| Resistance to vibration To EN 60068-2-6
|
10...55 Hz, Amplitude 0,35 mm
|
|
|
| Ambient conditions
|
|
|
| Ambient temperature
|
| - Min. environmental temperature
|
−25 °C
|
| - Max. environmental temperature
|
+45 °C
|
| Storage and transport temperature
|
| - Min. Storage and transport temperature
|
−40 °C
|
| - Max. Storage and transport temperature
|
+85 °C
|
| Protection class
|
| - Protection class-Enclosure
|
IP40
|
| - Protection class-Terminals
|
IP20
|
| - Protection class-Clearance
|
IP54
|
| Air clearances and creepage distances To IEC/EN 60664-1
|
| - Rated impulse withstand voltage Uimp
|
4 kV
|
| Overvoltage category
|
II To VDE 0110
|
| - Degree of pollution
|
2 To VDE 0110
|
|
|
| Electromagnetic compatibility (EMC)
|
|
|
| EMC rating
|
conforming to EMC Directive
|
|
|
| Electrical data
|
|
|
| Rated DC voltage for controls
|
| - Min. rated DC voltage for controls
|
-
|
| - Max. rated DC voltage for controls
|
-
|
| Rated AC voltage for controls, 50 Hz
|
| - Min. rated AC voltage for controls, 50 Hz
|
48 V
|
| - Max. rated AC voltage for controls, 50 Hz
|
240 V
|
| Rated AC voltage for controls, 60 Hz
|
| - Min. rated AC voltage for controls, 60 Hz
|
48 V
|
| - Max. rated AC voltage for controls, 60 Hz
|
240 V
|
| Contact resistance
|
max. 100 mΩ
|
| Power consumption
|
max. 2.8 VA
|
| Type of actuation
|
AC
|
| Switch frequency
|
max. 5 Hz
|
| Rated operating voltage Ue
|
48 ... 240 VAC
|
| Frequency range
|
50 / 60 Hz
|
| Electronic protection (Y/N)
|
Yes
|
| Fuse rating for the operating voltage
|
primary side F1: Safety fuse, tripping current > 0,5 A secondary side: Internal electronic trip, tripping current > 0,12 A
|
| Current and tension on control circuits
|
| - S11, S12, S21, S22, X2, X3
|
24 VDC, Test current: approx. 45 mA
|
| Bridging in case of voltage drops
|
70 ms (48 VAC); 270 ms (240 VAC)
|
|
|
| Inputs
|
|
|
| Monitored inputs
|
| - Short-circuit recognition (Y/N)
|
No
|
| - Wire breakage detection (Y/N)
|
Yes
|
| - Earth connection detection (Y/N)
|
Yes
|
| Number of shutters
|
0 piece
|
| Number of openers
|
2 piece
|
| Cable length
|
1500 m with 1.5 mm²; 2500 m with 2.5 mm²
|
| Conduction resistance
|
max. 40 Ω
|
|
|
| Outputs
|
|
|
| Stop category
|
0
|
| Number of safety contacts
|
3 piece
|
| Number of auxiliary contacts
|
1 piece
|
| Number of signalling outputs
|
0 piece
|
| Switching capacity
|
| - Switching capacity of the safety contacts
|
max. 250 VAC, 6 A ohmic (inductive in case of appropriate protective wiring)
|
| - Switching capacity of the auxiliary contacts
|
24 VDC, 2 A
|
| Fuse rating
|
| - Protection of the safety contacts
|
6.3 A slow blow
|
| - Fuse rating for the auxiliary contacts
|
2 A slow blow
|
| Utilisation category To EN 60947-5-1
|
AC-15: 230 V / 6 A DC-13: 24 V / 6 A
|
| Number of undelayed semi-conductor outputs with signaling function
|
0 piece
|
| Number of undelayed outputs with signaling function (with contact)
|
1 piece
|
| Number of delayed semi-conductor outputs with signaling function.
|
0 piece
|
| Number of delayed outputs with signalling function (with contact).
|
0 piece
|
| Number of secure undelayed semi-conductor outputs with signaling function
|
0 piece
|
| Number of secure, undelayed outputs with signaling function, with contact.
|
3 piece
|
| Number of secure, delayed semi-conductor outputs with signaling function
|
0 piece
|
| Number of secure, delayed outputs with signaling function (with contact).
|
0 piece
|
|
|
| LED switching conditions display
|
|
|
| LED switching conditions display (Y/N)
|
Yes
|
| Number of LED´s
|
3 piece
|
| LED switching conditions display
|
| - The integrated LEDs indicate the following operating states.
|
| - Position relay K1
|
| - Position relay K2
|
| - Supply voltage UB
|
|
|
| Miscellaneous data
|
|
|
| Applications
|
Emergency-Stop button
Guard system
Pull-wire emergency stop switches
|
|
|
| Dimensions
|
|
|
| Dimensions
|
| - Width
|
22.5 mm
|
| - Height
|
100 mm
|
| - Depth
|
121 mm
|
|
|
| notice
|
|
|
| Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.
|
|
|
| notice - Wiring example
|
|
|
| Input level: The example shows a 2-channel control of a guard door monitoring with two position switches, whereof one with positive break, external reset button (R) and feedback circuit (H2).
|
| The control recognises cable break in the monitoring circuit.
|
| Relay outputs: Suitable for 2 channel control, for increase in capacity or number of contacts by means of contactors or relays with positive-guided contacts.
|
| For 1-channel control, connect NC contact to S11/S12 and bridge S12/S22
|
| Automatic start: The automatic start is programmed by connecting the feedback circuit to the terminals S12/X3. If the feedback circuit is not required, establish a bridge
|
| The wiring diagram is shown with guard doors closed and in de-energised condition.
|
|
K.A. Schmersal GmbH & Co. KG, Möddinghofe 30, D-42279 Wuppertal The data and values have been checked throroughly. Technical modifications and errors excepted. Generiert am